GLOBAL ELECTROMECH (M) SDN BHD

犀利士台灣購買網站https://yescialis.com/,服用一片即可任意享受性福。需求大的ED患者,建議购买犀利士,網站地址https://www.cialislilly.com/比較合適,還可以選擇5mg低劑量,可以天天服用。

Automatic Main Failure Panel Board CW Synchronizing Panel
GESB-80-08-03-03

Automatic Main Failure Panel Board


Metering & Control Panel Generator Set No. 1
This unit should equip with the following:

  1. 1 x 250A Motorized circuit breaker, TP&N, 50Hz, 50kA c/w under voltage trips coil.
  2. 1 x Neutral contactor
  3. 1 x Neutral isolator
  4. 1 x Over current relay.
  5. 1 x Earth fault relay.
  6. 1 x Set of Current transformer for protective relay.
  7. 1 x Set of Current transformer for measuring meters and synchronizing modules.
  8. 1 x Voltmeter c/w selector switch.
  9. 1 x Ammeter c/w selector switch.
  10. 1 x Kilowatt meter.
  11. 1 x Digital power meter.
  12. 1 x Kilowatts hour meter.
  13. 1 x Power factor meter.
  14. 1 x Frequency meter.
  15. 1 x Reverse power relay
  16. 3 x Phase indicating light.
  17. 1 x Set of control fuses.
  18. 1 x Synchronizing key switch.
  19. 1 x Anti-Condensation heater c/w thermostat & switch
  20. 1 x Set of AMF Control Panel consists of generator set signal pilot lamps, HR meter battery charger, DC Ammeter and DC Voltmeter.
  21. 1 x Set of Selector control switches.
  22. 1 x Set of Generator control buttons.

Metering & Control Panel, Generator Set No. 2
This unit should equipped with the following.

  1. 1 x 250A Motorized circuit breaker, TP&N, 50Hz, 50kA c/w under voltage trips coil.
  2. 1 x Neutral contactor
  3. 1 x Neutral isolator
  4. 1 x Over current relay.
  5. 1 x Earth fault relay.
  6. 1 x Set of Current transformer for protective relay.
  7. 1 x Set of Current transformer for measuring meters and synchronizing modules.
  8. 1 x Voltmeter c/w selector switch.
  9. 1 x Ammeter c/w selector switch.
  10. 1 x Kilowatt meter.
  11. 1 x Digital power meter.
  12. 1 x Kilowatts hour meter.
  13. 1 x Power factor meter.
  14. 1 x Frequency meter.
  15. 1 x Reverse power relay
  16. 3 x Phase indicating light.
  17. 1 x Set of control fuses.
  18. 1 x Synchronizing key switch.
  19. 1 x Anti-Condensation heater c/w thermostat & switch
  20. 1 x Set of AMF Control Panel consists of generator set signal pilot lamps, HR meter battery charger, DC Ammeter and DC Voltmeter.
  21. 1 x Set of Selector control switches.
  22. 1 x Set of Generator control buttons.

Auto / Manual Synchronizing Panel
This unit should equipped with the following:

  1. 1 x Double voltmeter
  2. 1 x Double frequency meter.
  3. 1 x Synchronoscope.
  4. 2 x Synchronizing lamp.
  5. 1 x Voltage trimmers.
  6. 1 x Speed control trimmer.
  7. 1 x Auto synch module.
  8. 1 x Load sharing module.
  9. 3 x Synchronizing key switch
  10. 1 x Set of indicating lights
  11. 1 x Set of Control button for generator.
  12. 2 x Emergency buttons.

Output Panel

  1. 600A Auto Transfer Change Over Switch
  2. 600A 4 Pole Isolator
  3. 600A 4 Pole Change Over Switch

Overall Dimensions

Approximate: 4000W x 1000D x 2000H